Alarms and Warnings Check

Alarms/Warnings tracking and Suggestion page

 

Here in this page, all available alarms and warnings are listed which are available in "Status" page ( Monitoring / Status). 

For any alarm / warning, specific icons are shown to consult more information about that warning /alarm;   

IconDefinition
The icon is shown when that specific parameter has alarm condition. User may click on this icon to see details for that alarm
The icon is shown when that specific parameter has warning condition. User may click on this icon to see details for that warning

 

The page Status is consisted of 4 different classification groups as below:

  • Status
  • Ekip Modules
  • Circuit Breaker
  • Sense Accessories

 

Please find below detailed troubleshooter for each section and relative parameters

Status

Status section is regarding all status condition for Emax3 and consisted of parameters System check, Warnings and Alarms. 

Status parametersCauses / suggestions for parameter
System Check

Alarm status:

if present Any Alarm, Any Timing or any Trip in system

Warning status:

if present Any Warning in system

WarningsIf present Any warning
AlarmsIf present Any Alarm, Any Timing or any Trip in system

 

Ekip Modules

Ekip Modules section is consisted of parameters power supply, communication Internal Bus and Communication Field Bus.

Ekip Modules parametersCauses / suggestions for parameter
Power SupplyNo alarm/warning status. Only disconnection information is avaiable
Communication Internal Bus

Alarm status:

Local Bus

Unit on with auxiliary supply, Local Bus parameter enabled but connection to modules not present, incorrect or communication lost (for more than five seconds). Check connection and powering of modules in terminal box or external and verify the modules connected are compatible with Ekip Aware.

Warning status:

Communication Internal Bus

Communication issues between one or more Ekip modules and the trip unit (Bus overload, Faulty modules, Incorrect addressing or configuration)

Communication Field Bus

Alarm status:

Ekip Link Bus Error

Ekip Supply Evo Modbus TCP module fault: check for loss of connection to one or more actors (modules) connected to Link Bus.

Switchboard Actor communication Error

Check configuration and connection of Ekip Supply Evo Modbus TCP module

Warning status:

No warning status

 

Circuit Breakers

Circuit breakers section is consisted of CB Status, Breaker Switching Time , Breaker internal Temperature, Current Sensor L1,L2,L3, Ne,Gext, Trip Unit Status, Protections

Circuit Breaker parametersCauses / suggestions for parameter
CB Status

Alarm status:

Contact Wear

Make sure that the contacts/poles are in good condition.

Contact failure

Check the status of the contacts/poles

Warning status:

CB status

CB state incorrect (example: current present but CB in open state)

CB undefined

Check the circuit-breaker status signal contacts

CB Contact wear

Make sure that the contacts/poles are in good condition.

Breaker Switching Time

Alarm status:

Alarm status is not available

Warning status:

Breaker Switching time

This warning indicates that the circuit breaker is taking longer than expected to open or close. A common root cause is an issue with the operating mechanism, such as mechanical wear, lack of lubrication, or internal obstructions. Delayed switching can affect protection performance, so timely inspection and maintenance of the mechanism are recommended.

Breaker internal Temperature

Alarm status:

Sense sensor connection

Sense Sensor has been enabled, but module does not appear to be present.

T alarm || T alarm (Blocked Trip)

Abnormal temperatures recorded by the protection trip unit. Verify the limit of T protection CB

Temperature Alarm:

TBD

CB Temperature Alarm Blocked Trip

TBD

Smart Sensor warning

At least one temperature sensor disconnected from Sense accessories for Booster, Predictive Maintenance On Premise, Real Temperature protection packages

CB Temperature Warning/Alarm

This alarm indicates that the circuit breaker is operating at an abnormally high temperature. Possible root causes include mobile contact breakage, arc chamber wear, excessive contact wear, or foreign objects between the mobile and fixed contacts. Additionally, loose busbar connections at the breaker’s terminals can increase resistance and generate excess heat. Prompt inspection is recommended to prevent damage or failure.

Warning status:

T pre alarm

Temperature outside the operating range, Check the limits of the Protection T.

CB temperature warning

This alarm indicates that the circuit breaker is operating at an abnormally high temperature. Possible root causes include mobile contact breakage, arc chamber wear, excessive contact wear, or foreign objects between the mobile and fixed contacts. Additionally, loose busbar connections at the breaker’s terminals can increase resistance and generate excess heat. Prompt inspection is recommended to prevent damage or failure.

Current Sensor L1,L2,L3, Ne,Gext

Alarm status:

Sensor L1,L2,L3,Ne,Gext

Fault in connection of Ekip Aware sensors; check state of sensors, including external Neutral and Earth fault of MDGF if present, or contact ABB. Check current sensors, state of terminal and cables connecting to Ekip Aware.

Warning status:

Warning status is not available

Trip Unit Status

Alarm Status:

Internal Error

Internal error; contact ABB if this type of error occurs

Warning status:

Display OFF for temperature warning

Display off owing to operating temperature off-range, check limits in T protection

Battery low 

Replace the battery. Please be aware that the battery may explode unless it is handled correctly: do not charge, disassemble or burn. Only use batteries supplied by ABB. Use of other batteries could lead to the risk of fire or explosion.

Maintanence 

Perform maintenance and then reset the alarm via Ekip Connect

ProtectionsCauses of alarm and warning must be consulted from Alarms/Warnings page in EKIP Connect

 

Sense Accessories

Sense Accessories section is consisted of Trip Coil, M-Sense Enabler, Sense coils (YO1-Sense, YO2-Sense, YC1-Sense, YC2-Sense, YU1-Sense, YU2-Sense )

Sense Accessories parametersCauses / suggestions for parameter
Trip Coil

Alarm status:

Trip Coil disconnected

Disconnection of Trip coil detected, check functionality. Check Trip coil, state of terminal and cables connecting to Ekip Aware.

Trip fail command 

CB has not opened and/or current still present after a TRIP command: comply with the procedure described in chapter Faults, causes and remedies.

Warning status:

Warning status is not available

M-Sense Enabler

Alarm status:

Sense Motor

Alarm information from M-SENSE ENABLER (high temperature of device, communication error, alarm charge time)

Warning status:

Warning status is not available

Sense Coils

Alarm status:

Sense Coil

Alarm information about Sense version coils (high temperature of device, error in communication with protection release, last launch failed).

Warning status: 

Sense coil voltage out of range

The supply voltage read from the coil is below the minimum threshold or above the maximum threshold and a warning is generated

 

 

Cell THCell THCell THCell TH
CellCellCellCell