                                Power Controller: what it looks like
                            | 
			 Element 
			 | 
			Description | 
|---|---|
| Average power limit | Active power limit defining whether to disconnect/reconnect loads. | 
| Measurement time | Time interval during which power consumption is recorded and the average value calculated. The average value is compared with the set average power limit. | 
| Number of loads/generators monitored | 
			 Number of loads/generators monitored. 
			The system checks that the number of configured loads is consistent with this value... 
			 | 
		
| External synchronisation signal | Signal defining when to start the measurement time. | 
| 
			 Element 
			 | 
			Description | 
|---|---|
| 
			 User type 
			 | 
			Load type. If set as generator, the load is excluded from the function algorithm. | 
| Enabled | Includes/excludes the load from the function algorithm | 
| Name | Name assigned to the load | 
| Power consumption | Rated power of the load | 
| Disconnection priority | Position of the load in the load disconnection sequence. Priority 1 corresponds to the first load to be disconnected. | 
		
| Minimum reconnection time | Minimum load connection time to avoid power-on/power-off too close together. | 
| Disconnection time | Minimum disconnection time to avoid frequent power-on and off. Maximum disconnection time to avoid prolonged disconnections.  | 
		
| Time window | Period of the day during which the load cannot be disconnected. During that period the function algorithm excludes the load. | 
| 
			 Element 
			 | 
			Description | 
|---|---|
| Signal status/Commands > Contact | Device cable used for signal.
			
  | 
		
| Signal status > Meaning | (only if the device used for the signal is a circuit breaker and the optional status signal is activated). Meaning of the status signal: 
  | 
		
| Signal status > Polarity | Active open: if the input contact is open, the function interprets the load as active (closed). Active Closed: if the input contact is closed, the logic interprets the load as active (closed).  | 
		
| Signal status > Delay | Delay in seconds before the signal is processed after reception |